Critical Environment Technologies ART Instrukcja Użytkownika Strona 7

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 12
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 6
SIX
6
www.aamatrix.com
Venturi Air Valve
Available in a range of sizes
Stainless steel control rod
Baked phenolic P403 Heresite
®
powder coating
Zero leakage model available
Teon
®
(optional)
Venturi valve is a factory calibrated device
Sash Position Sensor
Compact, durable, long
cable life
Withstands impacts and
chemicals
Designed for high-cycle
applications
BACnet Fume Hood Controller
50ms response time
18-bit input resolution
Dedicated full color display
Native BACnet
PID control of face velocity (optional)
Electronic Damper Actuator
1.5 second travel time through 90˚ rotation
Exclusive long-life design
Non-contact internal control feedback
Capacitance-based fail safe position control
Fume Hood Display
272x480 pixel, color TFT display
Icon-driven touch screen interface
Audible and visual alarm indications
Monitor and modify inputs and control
parameters
Displays real time fume hood operating
conditions
Hood setup routines built-in with no need
for secondary software
Patent Pending
Made in the U.S.A. (0608a)
The American Auto-Matrix logo is a registered trademark of
American Auto-Matrix, LLC. © American Auto-Matrix, LLC. 2006
CRITICAL ENVIRON MENTS
Fume Hood Co ntroller
SBC-GPC
FHC1
NB-GPC
FHC1
SBC-GPC
FHC2
NB-GPC
FHC2
The Sash Position approach represents a widely accepted method designed to control face velocity base on calculations
configured directly into the controller. Face velocity is controlled by calculating the flow area based on sash position and
then controlling a calibrated air valve.
Secondary air flow feedback is also possible. The Sash Position method uses polymer coated string pots, a linear airflow
valve, and a differential pressure switch to regulate face velocity.
Press For Emergency
Main Men u
Face Velocity
100.1 fpm
Facevelocitycalculatedbyconguredsash
position;alsoconsidersbypassowand
hood leakage
Complete closed loop control based on
exhaustowismadepossibleusing
secondaryowmeasurement(optional)
High-speed tunable PID control algorithms